Synthesis™ Parallel Pump
Synthesis™ Parallel Pump Control regulates the pressure of a recirculating fluid system using multiple pumps that operate in unison.
Synthesis™ Parallel Pump Control regulates the pressure of a recirculating fluid system using multiple pumps that operate in unison.
Synthesis™ Parallel Pump Control regulates the pressure of a recirculating fluid system using multiple pumps that operate in unison. The program seamlessly integrates motor-control, logic, and process-control functions into a single, compact solution. With its sophisticated pump-modeling technology, the controller leverages the computing power of its digital signal processor (DSP) to provide superior control, optimal efficiency, and comprehensive protection for the pumping system.
Synthesis™ Parallel Pump Systems are available as stand-alone components or turn-key packages. Various standard packages and packaging options are available. Custom integration can be provided to meet any requirements.
The application can coordinate up to three pumps in parallel, each of which is controlled by a separate drive. One pump is the master of the system and responds to multizone differential pressure and flow feedback. The remaining slave pumps are synchronized with the master so that all pumps run at the same speed. As demand fluctuates within the system, the master stages the slaves as necessary to maintain constant pressure and maximize efficiency.
UNICO’s Pumping System Intelligence™ (PSI) technology mathematically models pump operation to achieve optimal performance, efficiency, and pump life. With just a few points from a pump’s published performance curve, the drive can dynamically calculate key variables such as developed head, flow, and efficiency to determine the most efficient staging under all operating conditions. By knowing the pump curve, the controller inherently protects against end-of-curve, cavitation, deadheading, and other damaging conditions by avoiding them altogether.
Unlike traditional controls, which turn pumps on and off based solely on speed, the master can stage the slave pumps based upon speed, flow, power, efficiency, or a combination of these conditions. Intelligent staging eliminates needless cycling and provides smooth, efficient performance.
All drives operate from identical control software and receive the same inputs. Each drive continually monitors the status of the others. If the master should fail, one of the slaves will assume its role so that operation continues without interruption.
For distributed systems, up to four pressure zones may be defined, each with its own setpoint. The control always identifies and caters to the zone with the greatest demand.
Parallel Pump systems can operate up to three pumps in speed synchronization.
Each pump is controlled by a flux vector AC drive from UNICO’s 1100 family. Drives are available from 11/2 to 500 hp and are UL and C-UL listed. Input power can be 230, 460, or 575 V AC.
Manual or fully automatic bypass control is available with packaged systems.
A variety of options is available for conditioning the incoming line, including AC line reactors, isolation transformers, twelve-pulse transformers, and harmonic filters.
Systems can be packaged in NEMA 1, 4, 3R, or 12 enclosures for indoor or outdoor use. Customization is available for special environmental requirements.
A touch-sensitive color interface simplifies start-up, operation, and troubleshooting. Users are walked through the commissioning process step by step. Once running, graphical screens portray system status, while an interactive diagnostic system provides assistance in the event of a problem.
Comprehensive start-up assistance, service, and training are available.
The following inputs and outputs are provided for interfacing the pump controller with the pumping system:
Inputs | Analog Inputs | Outputs | Analog Output |
local start | pump 1 flow | pump 1 bypass | analog communication |
remote start | pump 2 flow | pump 2 bypass | |
bypass 1 contactor | pump 2 flow | pump 3 bypass | |
bypass 2 contactor | zone 1 pressure | drive OK | |
bypass 3 contactor | zone 2 pressure | pump 2 start | |
pump 1 pressure switch | zone 3 pressure | pump 3 start | |
pump 2 pressure switch | zone 4 pressure | alarm | |
pump 3 pressure switch | slave speed | ||
partner A OK | suction pressure | ||
partner B OK | |||
slave enable | |||
communication bit 1 | |||
communication bit 2 | |||
communication bit 3 |
Our sales professionals are eagerly awaiting your questions. Fill out the form below and we’ll be in touch. If you’re looking for product support click here
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics". |
cookielawinfo-checkbox-functional | 11 months | The cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional". |
cookielawinfo-checkbox-necessary | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary". |
cookielawinfo-checkbox-others | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other. |
cookielawinfo-checkbox-performance | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance". |
viewed_cookie_policy | 11 months | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data. |